Transformer

DEWA Comments Regarding Transformer Rating.

Date:               xxx

Ref:                  xxx

Kind Attn         :Mr. xxx

Project:            2B + G + 14+ Lower Roof Hotel Building on Plot No. xxx at Al Barsha 1st, Dubai

Subject:               DEWA Comments Regarding Transformer Rating.

Dear Sir,

With reference to the above subject, our meeting with your MEP team and kindly note the following.

  1. We received comment from DEWA on dtd: 23-08-2017 regarding LV Panel-01 that reduce the breaker size from 2400 A to 1600 A.  So Transformer size will change from 1500 KVA to 1000 KVA.  
  2. As we explain explain about the D gradation of the transformer you advise us to provide spare load in load schedule by distributing in the basement and other areas.
  3. We are adding the additional spare load as per our discussion and your instruction at basement and ground floor to maintain the transformer size/capacity as per our original approval by maintaining the design load for the project.

So, we will revise the load schedule as per your inspection and same will be submitted for your review prior to submission to DEWA.

This is for your kind information and record.

Regards,

For xxx Contracting L.L.C.

xxx

Project Manager