CHECK LIST FOR: INSTALLATION of FIRE PUMPS SET | Form No: Rev. No: 00 Page : 1 of 1 | ||||
SUBCONTRACTOR | X | CONTRACTOR | |||
SECTION OF WORK: PLUMBING LOCATION: LEVEL: WIR No.: | |||||
STAGE | ITEM | Checked by | Checked by | Date | |
S/C | CONT | Cons. | |||
SETTING OUT | Check Layout. | ||||
Check Level. | |||||
Check materials are as per approved material submittal. | |||||
MEP/CIVIL | Check for Services Clearances. | ||||
Installation | Ensure the pumps installation is as per the manufacturer’s recommendations & as per approved detailed shop drawings. | ||||
Check base frame level using spirit level. | |||||
Check the pumps cabling & termination using megger. | |||||
Check whether the priming of the pumps are done properly and ensure the air lock is removed from the system. | |||||
All level float switches and dry run protections are properly installed. | |||||
Ensure that Pumps are free to rotate with hand. | |||||
Check pumps alignment using dial gauge or alignment tool. | |||||
Check that the control panels are integrated with the BMS System. | |||||
Check the smooth running of the pumps set overloads. | |||||
Ensure all piping and its joints are pressure tested. | |||||
Safety Precautions | When installing the Pumps, be mindful of the pump’s centre of gravity & weight. Ensure that the pump is suspended properly. | ||||
Ensure that only authorized personnel shall install the fire pumps set. | |||||
Install the pumps on a horizontal and rigid surface such as concrete, in an area that is free from turbulence and does not cause the pump to take air in. | |||||
Properly install pipes so as not to create any air pocket in the middle of the piping. | |||||
Place the pump and the float switch away from the inlet or install a baffle plate. | |||||
For S/C QA/QC: | Date: | FOR CONTRACTOR QA/QC: | Date: | For Consultant Rep.: | Date: |
Name: | Sign: | Name: | Sign: | Name: | Sign: |