Shop Drawing

Shop Drawing

Date: xxx

Ref no: xxx

To             :M/s xxx Center

Project     : 2B + G + 14+ Lower Roof Hotels Building on Plot No. xxx at Barsha,  Dubai

Subject     : Your shop drawing submission for joinery and doors on dated xxx

Dear Sir,

With reference to the above, regarding your transmittal form and submittal ref no.cm-al-bar-269-hc-tr001on dated 15.03.17, kindly find our review report:

  1. We must require covering letter from the home center with the reference no.of the transmittal and brief statement about the document on home center letter head.

So, kindly honour the privity of the contract.

a) Back up ply of the mirror is not the part of chirag contractor’s scope. It should be fixed by Home center which is shown in your fixing detail .

b) Sliding door fixing details are different (In ID drawings and Home center drawings)

b) We need sliding door to be fixed in mock up room ,   interconnecting door is not showing architrave also, required full details.

       4)  In the drawing no.Guest room TV panel , you have mentioned “as warm LED light by others” and please note that, this is not Main contractor’s scope. Kindly contact to M/s Citymax and assign the responsibility after discussion with them.

 We are attaching the template, please submit the drawing as per the template attached.

            So, kindly resubmit the drawings and provide sliding door at mock up room and incorporate other missing things

Regards,

For xxx Contracting L.L.C

xxx

Project Manager